Reference | I/O Devices Synch Cycle : Enter the cycle time for the synch telegram send. Baudrate : Used to set the baud rate used for CAN bus operation. Watchdog : Watchdog, used by the CANopen card to monitor TwinCAT. AutoClear : If you select this box, a node failure will halt the whole network. Otherwise, the system attempts to re-incorporate the node and continues operating. Synchronous Mode : The highest priority task linked with a corresponding device controls the fieldbus cycle and is thereby synchronized with the fieldbus I/O update (but not with CANopen SYNC; this is an independent card function). All other tasks are served asynchronously via corresponding buffers.
Firmware Update ... Update the CIF-30 CAN firmware version here. The currently loaded firmware version is shown in the window - in red if the TwinCAT recognizes and is awaiting a more recent version. Tab ”(Online) DPRAM” See ” Online Display of DPRAM [ } 267] Input Diagnosis The CIF-30 automatically provides four input bytes which describe the status of the card and the CAN bus: GlobalFlags : The individual bits have the following definitions: 0x01 = Ctrl: Parameterization error 0x02 = ACtrl: Device stopped communication because of a guarding error at a node. 0x04 = NData: At least one node failing to communicate or has a configuration error 0x08 = Fatal:
Serious bus error occurred 0x10 = Event: Communication error recognized 0x20 = NRdy: Host is not ready ErrorRemAddr : Address of the node sending the signal, address 255 is the master card itself EventError : If ErrorRemAddr is other than 255 the following applies: =30: Guarding malfunction =31: Node has changed status =32: Sequence error in guarding protocol =33: No answer from remote frame PDO =34: No answer during a node configuration =35: Incompatible node profile number =36: Incompatible node device type number =37: Unknown SDO response received =38: SDO syntax error =39: Node in STOP mode TwinCAT 2 181 Version: 1.7