Reference | I/O Devices The Ethernet adapter currently selected is shown on this "Adapter" tab. Search... : Looks for TwinCAT Real-Time Ethernet compatible devices [ } 239] and displays them. MAC Address: MAC Address of this Ethernet controller IP Address: Settings taken from Windows Registry. These can be changed under "Control Panel | Network Connections" in the TCP/IP 'Properties ..' section.. If Real-Time Ethernet and "normal" Ethernet are both used on the same system with two different network adapters, the subnet addresses of these adapters (NICs) must differ!
Nevertheless, the Real-Time Ethernet belonging devices have to be configured with the same subnet address (first two quadruples) as the Ethernet Miniport adapter and vice-versa, of course. Freerun Cycle : The cycle time used if Free-Run [ } 22] is active ( Config Mode [ } 13] only), can be set here. The cycle time in Run mode results automatically in reference to the task with the highest priority linked to the variables of the adapter or one of its nodes. Lock I/O after Link Error : If this box is checked, the process data exchange doesn't resume automatically after a resolved link problem (e.g. when the network cable has been unplugged).
In such a situation, an I/O Reset is necessary afterwards, instead. Promiscuous Mode(use with Netmon/Ethereal only): This check box should only be enabled, if one wants to capture the network traffic with tools like Ethereal or the Microsoft Network monitor. If this box is checked, the Real-Time Ethernet miniport device copies all frames to the NDIS protocol layer of windows. This allows protocol drivers to capture the frames. TwinCAT 2 199 Version: 1.7