Reference | I/O Devices Actual State: Shows the current state of the EtherCAT master device. Send Frames: Shows the number of frames sent by the EtherCAT master device. Frames: Shows the number of sent frames per second. Init: Requests the 'Init' state from the master. Pre-Op: Requests the 'Pre-Op' state from the master. Safe-Op: Requests the 'Safe-Op' state from the master. Op: Requests the 'Op' state from the master. Clear CRC: Clears the CRC counters of the EtherCAT slave devices. ClearFrames: Resets the counter displayed in the "Send Frames" edit box to 0. The list view shows all the EtherCAT slave devices and their corresponding states and CRC counters:
To request a specific state from an individual EtherCAT slave device one must right click on the slave device in the list view. This opens following context menu: TwinCAT 2 201 Version: 1.7 Column Description No Physical position of the device in the communication ring Addr Fixed address (see EtherCAT Addr) of the slave device. Name Name of the EtherCAT device State State of the EtherCAT slave device. The state can be either INIT, PRE-OP, SAFE-OP or OP. If the device cannot be found by the master or the slave is unable to change the state, ERR + the last known valid state is displayed. CRC CRC counter of the EtherCAT slave device.
If an individual slave device is selected in the list, the CRC counters of the ports A,B and C(if in use) are listed in brackets.