Reference | Boxes ”BK4xx0” tab Identity Code : Displays the identity code for the Bus Coupler. It is calculated dynamically - according to the connected terminals. Length Code : Displays the length code for the Bus Coupler. It is calculated dynamically - according to the connected terminals. Installation depth : Displays the installation depth of the Bus Coupler. It is calculated dynamically - according to the hierarchical structure of the InterBus-S. Diagnostic : Inserts two bytes of diagnostic data into the process image per input and output (see BK4000 manual). 2 Byte PLC interface :
Inserts two bytes of PLC interface into the input and output process image Input Diagnosis Each InterBus-S box contains one diagnostic input byte which signals the status of the current slave during the running time and can be linked, for example with the PLC. 11.3.1.4 BK51x0/LC5100/IPxxxx-B510 (CANopen) | BK51x0/LC5100/IPxxxx-B510 (CANopen) The BK51x0 Bus Coupler and the IPxxx-B510 fieldbus box are installed in the CANopen bus. Those specific properties which distinguish them from other Bus Couplers and/or Fieldbus Box modules are described below. For an Overview [ } 320] of currently supported CANopen Bus Couplers BK51x0, see [ } 320] ... TwinCAT 2 280 Version:
1.7 Variable Value Description BoxState 0x01 Rec: Reconfiguration 0x02 Mod: Module error 0x04 W2Err: Error at the W2 interface 0x08 W1Err: Error at the W1 interface 0x10 W2: W2 interface inactive 0x20 W1: W1 interface inactive