beckhoff — 11.3.1.6 BK7500 (SERCOS interface)

Reference | Boxes ”BK75x0” tab Address : This is used to set the Sercos address with which the coupler announces its presence on the bus. K-Bus Update : Knowing the attached terminals, the estimated K-Bus run-time is calculated and given. Strict Mode : The manufacturer-specific parameter P-0-0001 can be used to specify whether the I/O data channels are to be allocated in strict accordance with the Sercos I/O specification, or whether a variation that saves IDNs should be used, since some controllers can only handle a limited number of IDNs in the Master Data Telegram (MDT) or Drive Telegram (AT). The checkbox on this tab only displays the selected mode.

It can be modified on the next tab, under Startup, because this parameter is communicated at each start-up (change from phase 2 to phase 3), and the I/O data channels are then assigned accordingly. Firmware Update ...: The coupler's firmware can be updated by means of what is known as a KS2000 cable. TwinCAT 2 287 Version: 1.7