Reference | Boxes Delete Box... Deletes the marked box and its sub-elements from the I/O configuration. Import Box... Adds another box above the marked box. The description of the new box and its sub-elements are read from a file with the suffix "*.tce". This file is created with the following menu option. Export Box... Exports the information from the selected box and the information about its sub-elements into a file with the suffix "*.ioe". Variables Beneath the box, four bytes each in/outputs are automatically defined which are addressed/linked either as bytes or as individual bits.
”32 bit” tab The individual variables can be linked at the same time for all variables via the ”32 bit” tab. You can of course still create the links using the context menu or the tab view for each variable. D0 Input ...: Opens the link dialogue for the first input byte / for a bit of the first input byte if you have selected bit-wise mode. If linking by bits you can select the relevant bit. D1 Input ...: ditto. 11.3.2.2 M2400 | M2400 The M2400 is an analog output box with up to four channels, which also has two digital data bytes. The box jumpers determine whether the data bytes function as input or output bytes (see M2400 manual).
If the box has less than four analog channels, the corresponding DACs are not linked. Data telegram only for the higher priority task If the box is linked to several tasks (e.g. DACs with NC and data bytes with PLC), the data telegram is only created for the higher priority task. This is particularly important during commissioning if, for example, only the PLC is running. Context menu Add Box... Adds another box above the marked box. TwinCAT 2 301 Version: 1.7