beckhoff — 11.3.3.1 GSD Device

Reference | Boxes ”Profibus” tab Stations No .: Each Profibus device requires a unique station number. Watchdog : Switches on a watchdog function. The time period (in ms) can be set when communication monitoring is actuated. The communication monitoring period should be at least 6 x greater than the cycle time. The minimum value is 10 ms. PrmData : Allows you to edit the Profibus-specific parameter data (-> BK3xx0 Bus Coupler documentation). The size of the current parameter data is displayed. The PrmData can be entered either in text form (-> PrmData (text)) or occasionally via tabs ”BK3xx0 / BC3x00”. CfgData :

Displays the current configuration data (produced on the basis of added terminals) and their lengths. The settings DP class 1, DP class 2, DPV1 class 2, Set and Reset slave are only activated for FC310x (-> PROFIBUS DP slaves at FC310x ) ”PrmData (text)” tab Click on a line to change the current value. TwinCAT 2 313 Version: 1.7