Reference | Boxes Under "Inputs" ( Actual Channel ) all necessary and optional SERCOS parameters which come from the drive fin this case, are listed. Corresponding variables are automatically created below the axis in the tree view. These can be linked accordingly. A position feedback value is required in all cases! New ...: After hitting this button, additional variables can be inserted into the cyclical receive telegram from the drive: At Id. No. , a supported IDN of the drive can be entered. Name is an edit field for a descriptive name for the IDN (suggested parameters from above shown list will fill this name field automatically).
Additionally, Accordingly, the appropriate data type for the wished IDN has to be selected from the list, shown on the right. ”Outputs” tab Variables, which must be transmitted to the drive, are specified here as in the "Outputs". Depending upon the axis operating mode, the list on this tab must contain the "Velocity command value" or the "Position command" value. Further parameters can be added in the same way as under "Inputs" here. ”ADS” tab The ADS port number, via which all ADS access to the internal drive parameters takes place, is entered here at the ADS tab [ } 49] . TwinCAT 2 343 Version: 1.7