Reference | Boxes 1 = Data Status, 2 = Name (read only), 3 = Attribute (see SERCOS specification), 4 = Unit, 5 = Minimum, 6 = Maximum Reset via ADS The drive amplifier can be reset (e.g. after exceeded max. lag-distance) via ADS. To the SERCOS IDN S-0-0099 an ADS Write command (or sequence) has to be sent. The command varies depending on the used SERCOS master card - FC7501 [ } 191] resp. FC7502 [ } 191] : a drive reset can be achieved if to IndexGroup : 0x0063, IndexOffset: 8, a 3 is send ( "ByRef" , that means in this case: The address of a constant 3 has to be passed on to SrcAddr ). or at a - SERCANS SCS-P Master card:
if the values 3 , 0 , 3 and 0 again, are sent "ByRef" ( SrcAddr ) one after another to IndexGroup : 0x0063, IndexOffset: 7. (By the way, this is done internally by the TwinCAT System Manager, if you press the "Reset" button on the "Online" tab). Diagnosis Inputs The Drive Status Word is a SERCOS specific return telegram, all SERCOS drives have to provide. TwinCAT 2 346 Version: 1.7