beckhoff — 11.3.9.2 Network Variable Subscriber

Reference | Boxes Context menu Insert Network Variable: Please see description under Subscriber [ } 351] Other items: Please see Adding Input/Output Modules [ } 100] Publisher variable - Outputs Requirements 11.3.9.2 Network Variable Subscriber | Network Variable Subscriber The Beckhoff TwinCAT Real-Time Ethernet [ } 409] solution contains from TwinCAT v2.9 on the ability to configure variables for deterministic data exchange between several TwinCAT-based controllers. The last could be other TwinCAT PCs or CX100x controllers. For this solution it is required to configure the Ethernet Miniport (Real-Time) [ } 239] I/O device type first.

For an Overview [ } 348] of TwinCAT Real-Time Ethernet devices, see.. [ } 348] The Subscriber is the receive-type variable of the TwinCAT target system. It receives values from the Publisher [ } 348] variable of the networked TwinCAT controller. TwinCAT 2 351 Version: 1.7 Variable Data type Description VarCtrl UINT Can be set to 0x0001 = Disable publishing The transmission of this publisher variable is suppressed in above case (until VarCtrl becomes '0' again). The subscriber CycleIndex [} 354] variable stays static and the Quality [} 354] counts up (to a maximum of 65535). VarData as specified [} 354] To be linked to the output variable (e.g.

PLC output) to be transmitted via TwinCAT Real-Time Ethernet.