beckhoff — 11.3.10.1 EtherCAT Slave Device

Reference | Boxes State Machine: Init: Tries to set the EtherCAT slave device to the Init State. Pre-Op: Tries to set the EtherCAT slave device to the Pre-Operational State. Safe-Op: Tries to set the EtherCAT slave device to the Safe-Operational State. Op: Tries to set the EtherCAT slave device to the Operational State. Bootstrap: Tries to set the EtherCAT slave device to the Bootstrap State. Clear Error: Tries to clear the error flag. If a slave device fails to change to another state, it sets the error flag. For instance, a slave device is currently in the Pre-Operational state. Then the master requests the Safe-Operational state.

If the slave device fails to change to Safe-Operational, it sets the error flag. The current state would be displayed as "ERR PREOP". After pressing the Clear Error, the error flag is cleared and the current state would be displayed as "PREOP" again. Current State: Current EtherCAT State of the slave device. TwinCAT 2 360 Version: 1.7