beckhoff — 12.1.2.1 Process Data Objects (PDO)

Appendix | Appendix A: Fieldbus Know how PDO transmission types: Parameterization The PDO transmission type parameter specifies how the transmission of the PDO is triggered, or how received PDOs are handled. Acyclic Synchronous PDOs of transmission type 0 function synchronously, but not cyclically. An RxPDO is only evaluated after the next SYNC telegram has been received. In this way, for instance, axis groups can be given new target positions one after another, but these positions only become valid at the next SYNC - without the need to be constantly outputting reference points.

A device whose TxPDO is configured for transmission type 0 acquires its input data when it receives the SYNC (synchronous process image) and then transmits it if the data correspond to an event (such as a change in input) having occurred. Transmission type 0 thus combines transmission for reasons that are event driven with a time for transmission (and, as far as possible, sampling) and processing given by the reception of "SYNC". Cyclic Synchronous In transmission types 1-240 the PDO is transmitted cyclically: after every ”nth” SYNC (n = 1...240).

Since transmission types can be combined on a device as well as in the network, it is possible, for example, for a fast cycle to be agreed for digital inputs (n = 1), whereas the data for analog inputs is transmitted in a slower cycle (e.g. n = 10). RxPDOs do not generally distinguish between transmission types 0...240: a PDO that has been received is set to valid when the next SYNC is received. The cycle time (SYNC rate) can be monitored (object 0x1006), so that if the SYNC fails the device reacts in accordance with the definition in the device profile, and switches, for example, its outputs into the fault state. TwinCAT 2 385 Version:

1.7 Transmission type Cyclical Acyclical Synchronous Asynchronous Only RTR 0 X X 1-240 X X 241-251 - reserved - 252 X X 253 X X 254, 255 X