Appendix | Appendix A: Fieldbus Know how 12.1.2.4 Bit Timing | Bit Timing The following baud rates and entries in the bit-timing register are supported by the CANopen devices: The bit-timing register settings given (BTR0, BTR1) apply, for example, for the Philips 82C200, SJA1000, Intel 80C527, Siemens 80C167 and other CAN controllers. They are optimised for the maximum bus length. 12.1.2.5 Identifier Allocation | Identifier Allocation Default identifier CANopen provides default identifiers for the most important communication objects, and these are derived from the 7-bit node address (the node ID) and a 4-bit function code in accordance with the following scheme:
For broadcast objects, the node ID is set to "0". This gives rise to the following default identifiers: Broadcast objects Peer-to-peer objects TwinCAT 2 392 Version: 1.7 Baud rate [kbaud] BTR0 BTR1 1000 00 14 800 00 16 500 00 1C 250 01 1C 125 03 1C 100 43 2F 50 47 2F 20 53 2F 10 6F 2F Object Function Function code resulting COB ID hex / dec Object for comm. parameter / map- ping NMT Boot up 0 0x00 / 0 - / - SYNC Synch. 1 0x80 / 128 0x1005 + 0x1006 / -