Appendix | Appendix B: Real-Time Ethernet Installation 12.2.2.1 Example | Example Based on the configuration described above you can now carry out a test with the following PLC project. In this example the server fetches a handle via ADS for a client variable and writes the value 500 to it. A useful application is shown in conjunction with ADS. Server: PROGRAM Server VAR state : UINT; trigger : R_TRIG; bExecute : BOOL; bBusy : BOOL; bError : BOOL; uErrorID : UDINT; fbWRI : ADSWRITE; fbRW : ADSRDWRT; uTransmit : UDINT := 500; uHandle : UDINT; sTest : STRING := 'MAIN.uReceive'; END_VAR trigger(CLK := bExecute); IF trigger.Q THEN state := 1; bBusy := TRUE; END_IF CASE state OF 0:
(* Wait state *) bBusy := FALSE; 1: fbRW( WRTRD := FALSE); fbRW( NETID := '172.16.2.94.2.1', PORT := 801, IDXGRP := 16#F003, IDXOFFS := 16#0000, WRITELEN := LEN(sTest)+1, READLEN := SIZEOF(uHandle), SRCADDR := ADR(sTest), DESTADDR := ADR(uHandle), WRTRD := TRUE, TMOUT := t#5s, BUSY => , ERR => bError, ERRID => uErrorID); state := 2; 2: fbRW( WRTRD := FALSE); IF NOT fbRW.BUSY THEN IF NOT fbRW.ERR THEN state := 3; ELSE state := 100; END_IF END_IF 3:
fbWRI( WRITE := FALSE); fbWRI( NETID := '172.16.2.94.2.1', PORT := 801, IDXGRP := 16#F005, IDXOFFS := uHandle, LEN := SIZEOF(uTransmit), SRCADDR := ADR(uTransmit), WRITE := TRUE, TMOUT := t#5s, BUSY => , ERR => bError, ERRID => uErrorID); state := 4; 4: fbWRI(WRITE := FALSE); TwinCAT 2 423 Version: 1.7