beckhoff — 12.4.2 Methods of the ActiveX control

Appendix | Appendix D: EtherCAT Topology ActiveX Control Property type Read-Only property Default value Syntax (C#) ECTOPOLOGYLib.TOPOLOGY_MASTER_STATE MasterState { get; } Member of IEcTopologyCtrl ShowCrcErrorMarker Description The property ShowCrcErrorMarker defines, if the existance of crc errors should be displayed graphically in the online view. If this value is true, a red circle for every ethernet port with a detected error is displayed beneath the EtherCAT slave.

Property type Read-write property Default value false Syntax (C#) bool ShowCrcErrorMarker { set; get; } Member of IEcTopologyCtrl ShowSlaveInfo Description The property ShowSlaveInfo defines, if the information dialog for the selected device should be displayed in the online view. The dialog is display in the right corner of the view and contains additional information about the EtherCAT slave Property type Read-write property Default value false Syntax (C#) bool ShowSlaveInfo { set; get; } Member of IEcTopologyCtrl TwinCAT 2 448 Version:

1.7 MasterState Description TOPOLOGY MASTER STATE INVALID _ _ _ Master is in an invalid state TOPOLOGY MASTER STATE INT _ _ _ Master is in the EtherCAT state Init TOPOLOGY MASTER STATE PREOP _ _ _ Master is in the EtherCAT state Pre-Operational TOPOLOGY MASTER STATE SAFEOP _ _ _ Master is in the EtherCAT state Safe-Operational TOPOLOGY MASTER STATE OP _ _ _ Master is in the EtherCAT state Operational TOPOLOGY MASTER STATE OFFLINE _ _ _ No connection to the master exists at the moment. This is the case for instance. if the the TwinCAT system is stopped.