SYSTEM Configuration | Real Time Settings If this entry is selected, the "Settings" dialog (described below), the " Online [ } 56] " and the " Priorities [ } 56] " dialog (described later) appear on the right-hand side in the System Manager. ”Settings” tab Base Time The TwinCAT schedulers change on every tick from Windows to the TwinCAT real time. The planned and necessary task is then performed in TwinCAT real time. By the time the CPU limit (see below) has been reached, the system has changed back to Windows. The TwinCAT basis time is therefore the shortest possible task cycle time. The cycle time can also be a multiple of the basis time.
The basis time should only be set to less than a millisecond if necessary and with correspondingly fast PC systems. The following are possible: (none), 1ms, 500µs, 333µs, 250µs, 200µs, 125µs, 100µs, 66µs and 50µs. TwinCAT can be used without executed real-time by setting the Bse Time value to none, realtime will not be executed. Implementations which donґt need real-time, work as usual (AMS Router, TwinCAT Scope, ADS OCX, ...) Restricitions: Real-time tasks, like PLC tasks, software tasks and I/O tasks (Profibus, DeviceNet, Sercos or Lightbus) cannot be executed.
CPU Limit Specify the CPU percentage proportion that completely fills the TwinCAT real time, the remainder is reserved for Windows (and for surface programs). The value can be set very high since it is automatically reset to Windows when the real time task has completed its cycle. Fast Tick Only for special TwinCAT extensions which require a rapid tick irrespective of basis time (e.g. camshaft controller). TwinCAT 2 55 Version: 1.7