SYSTEM Configuration | Real Time Configuration - Priorities 4.3 Real Time Configuration - Priorities | Real Time Configuration - Priorities In addition to the dialogues Settings [ } 54] and Online [ } 56] , contains the Real Time - Configuration area of the TwinCAT System Manager a dialog named Priorities . The dialog displays the priorities of the different tasks inside the TwinCAT System. With enabling of the Expert Mode [ } 20] it is even possible to change the priorities of the tasks, manually. "Priorities" tab Priority Each TwinCAT Task has its own Priority in the system. The priority number is shown in this column. The lower the number, the higher the priority of the task.
Additionally, each task type has a dedicated icon, shown in front of the number. Cycle Task cycle time in milliseconds. Task names the job of the task. At PLC tasks, it differs between PLC communication Task : This Task serves the ADS communication. To protect PLC data consistency, it should have the lowest priority level, referring to one PLC Run Time System. PLC Boost Priority: Priority of a PLC Task, as soon as it is in Monitoring / Debug mode. This Task should have the highest priority, referring to the Tasks of one PLC Run Time System. Common TwinCAT Task (light blue icon) for currently unused PLC Tasks reserved Priority (e.g. Task 1, 2 and 3 of a PLC Run Time System).