SYSTEM Configuration | Task Settings Name Edits the internal name of the task Port Defines the AMS port number of the task. This value must be specified! For some tasks the value is already set (e.g. for PLC tasks). Auto-Start Causes the TwinCAT System Manager to create the start command for the task so that when restarting TwinCAT the task is automatically started with the specified data. Priority Defines the Priority of the Task [ } 58] within TwinCAT (you should ensure that priorities are not duplicated). The priority is only relevant when Auto-Start is selected. Cycle Ticks Sets the cycle time in ticks (depends upon the pre-set TwinCAT Base Time [ } 54] ). of the task.
The cycle time is only relevant when Auto-Start is selected. Warning by exceeding Causes the TwinCAT to issue a warning when the pre-set task cycle time is exceeded. Message box Outputs the warning (above) also as a message box. I/O at task begin An I/O cycle is carried out at the beginning of the task. TwinCAT 2 63 Version: 1.7