beckhoff TE1000 — 4.2 Addition of publisher variables

Creation of an EAP configuration Appearance of the input and output variables The structure of the process image varies, depending on which port (network adapter of the PLC or an EL66xx Switch Port Terminal) the EAP device uses for communication. Description of the unconditional input/output variables FrameState The FrameState input variable below the Publisher node indicates the current state of the TxFrame. A detailed description can be found in the Publisher [ } 25] section. FrameCtrl The FrameCtrl output variable below the Publisher can be used to control the transmission of the EAP telegram. The following values are possible for FrameCtrl :

Appearance of the output variable FrameCtrl This variable does not exist in the case of EAP communication via the EL66xx terminal! Instead, the output variable CycleIdx (size: 16 bits) is created, which is to be used for a diagnosis of the communication connection (see Diagnosis of an EAP connection [ } 22] ). VarState The input variable VarState below the Publisher Variable indicates the current state of TxData. A detailed description can be found in the Publisher [ } 25] section. VarCtrl The output variable VarCtrl below the Publisher Variable can be used to control the transmission of the Publisher Variable . The following values are possible for VarCtrl :

Appearance of the output variable VarCtrl This variable does not exist in the case of EAP communication via the EL66xx terminal! CycleIndex The output variable CycleIndex below the TxProcessData should be linked with an application variable that is cyclically incremented, since the CycleIndex on the receiving side can be evaluated for diagnostic purposes (see Diagnosis of an EAP connection [ } 22] ). Appearance of the output variable CycleIndex The output variable CycleIndex only exists if the EAP communication takes place via the EL66xx terminal! This variable does not exist if the EAP communication takes place via a PC network adapter.

The CycleIndex in the EAP telegram is then automatically incremented with each task cycle. VarData The output variable VarData of the Publisher Variable can be linked with any desired variable of a suitable data type (e.g. with the variables of a PLC program). TE1000 30 Version: 1.7.1 Short description Bit Description Disable sending FC.0 The transmission of the frame is interrupted if the bit is set to 1. The transmission of the frame only restarts when the value falls back to 0. Remove destination MAC from ARP cache FC.1 This control box only has an effect if the EAP telegram is sent by IP or AMSNetID. The destination MAC address entered in the ARP cache is deleted if the bit is set.

A new entry can only be made when the bit is reset to 0, provided the EAP device can determine the destination MAC address by ARP. (see also Remote station monitoring via ARP [} 13]) Short description Bit Description Disable publishing VC.0 The transmission of the Publisher Variable is interrupted. The transmission of the Publisher Variable restarts only when the value of the bit has returned to 0.