The CANopen object dictionary It is not possible to change the configuration of the TwinCAT EAP device in TwinCAT if the option Recover Online Configuration is set. To do this the option must first be deactivated again. The sole purpose of this blocking mechanism is to protect the offline configuration against being changed by the user, even though this change would have no effect when activating the controller since the online configuration is restored. Recover online configuration The archived CANopen Object Dictionary is coupled to the instance of the EAP device in TwinCAT.
As soon as this instance is deleted in TwinCAT and a new instance is created instead, the previously archived OD can no longer be restored for this instance. TE1000 75 Version: 1.7.1