Overview of NC errors TwinCAT 15 Version: 1.1 Error(Hex) Error(Dec) Error type Description 4234 16948 Internal "PTP data type range exceeded" Such extreme parameters have been supplied for the start task, the override or the new target position that the internal data type loses its precision. 4235 16949 Function "PTP LHL velocity profile cannot be generated" (INTERNAL ERROR) Such extreme parameters have been supplied for the start task, the override or the new target position that it is not possible to generate a velocity profile of the type LHL (Low-High-Low).
4236 16950 Function "PTP HML velocity profile cannot be generated" (INTERNAL ERROR) Such extreme parameters have been supplied for the override or the new target position that it is not possible to generate a velocity profile of the type HML (High-Middle-Low). 4237 16951 Address "Start data address is invalid" The address of the start data is invalid. 4238 16952 Parameter "Velocity override (start override) is not allowed" The value for the velocity override is not allowed, because it is less than 0.0% or more than 100.0% (see axis interface PlcToNc). Here, 100.0 % corresponds to the integral value 1000000 in the axis interface. Value range: [0 ...
1000000] 4239 16953 Parameter "Start type not allowed" The start type supplied does not exist. 423A 16954 Monitoring "Velocity overflow (overshoot in the velocity)" The new dynamic with the parameterized jerk is so weak that a velocity overflow will occur (overshoot in the velocity). The command is therefore not supported. 423B 16955 Parameter "Start parameter for the axis structure is invalid" External or internal parameters for the start structure for a positioning task are invalid. Thus, for instance, the scaling factor, the SAF cycle time or the requested velocity may be less than or equal to zero, which is not allowed.
423C 16956 Parameter "Override generator initialization parameter invalid" One of the override generator (re)initialization parameters is invalid. 423D 16957 Monitoring "Slave axis has not set value generator" (INTERNAL ERROR) It is found that a slave axis within a group does not have a valid slave generator (set value generator). A slave axis and a slave set value generator must always be present as a pair. This is an internal error. 423E 16958 Function "Table is empty" Either the SVB table or the SAF table does not contain any entries. 423F 16959 Function "Table is full" The SVB table or the SAF table has no more free lines.
4240 16960 Memory "No memory available" SVB memory allocation for dynamic entry in SAF table failed. 4241 16961 Function "Table already contains an entry" (INTERNAL ERROR) SAF table entry abandoned, because, incorrectly, an entry already exists. 4242 16962 Function "Stop is already active" The stop instruction is not forwarded, because it has already been activated. 4243 16963 Function "Compensation has not been carried out over the full compensation section" The compensations start parameters do not permit compensation over the full section to be compensated. For this reason the compensation will be carried out over a smaller section.