PLCopen Motion Control iTcMc_EncoderKL2542 The function block handles the evaluation of data from a KL2542 motor output stage terminal. This I/O device belongs to a group of devices, which are used for the control value output as well as actual value determination. The required mapping definitions, particularly for parameter communication, overlap with those of the drive function block. See also iTcMc_DriveKL2542 [ } 133] . iTcMc_EncoderKL3002 The function block handles the evaluation of data from a KL3002 analog input terminal. iTcMc_EncoderKL3042 The function block handles the evaluation of data from a KL3042 analog input terminal. PLC Library Hydraulics 149 Version:
1.4 I/O variable Interface.Variable Use Velocity ST TcPlcDeviceOutput.nDacOut _ Operation: Output of the velocity signal. For register communication [} 233]: Interface for written data. Position ST TcPlcDeviceInput.uiTerminalD _ ata Operation: Read the actual position. For register communication: Interface for read data. Ctrl ST TcPlcDeviceOutput.bTerminal _ Ctrl Control the output stage, register communication. Status ST TcPlcDeviceInput.bTerminalSt _ ate Status of the output stage, register communication.
ExtCtrl ST TcPlcDeviceOutput.uiTerminal _ Ctrl2 Latch control during homing with the synchronous pulse of the encoder ExtStatus ST TcPlcDeviceInput.uiTerminalSt _ ate2 Diagnosis of output stage and motor, latch status during homing with the synchronous pulse of the encoder I/O variable Interface.Variable Use Data out ST TcPlcDeviceOutput.nDacOut _ Operation: Output of the velocity signal. For register communication [} 233]: Interface for written data. Data in ST TcPlcDeviceInput.uiTerminalD _ ata Operation: Read the actual position. For register communication: Interface for read data. Control ST TcPlcDeviceOutput.bTerminal _ Ctrl Control the output stage, register communication.
Status ST TcPlcDeviceInput.bTerminalSt _ ate Status of the output stage, register communication. I/O variable Interface.Variable Use Data in ST TcPlcDeviceInput.uiCount _ Read the actual position. Ctrl ST TcPlcDeviceOutput.usiCtrl _ Register communication [} 233] Status ST TcPlcDeviceInput.usiStatus _ Register communication.