TwinCAT PLC Library Hydraulics - Version 1.4 — 5.1 FAQs (from V3.0)

Knowledge Base Transition between a fast and a slow section. FAQ #21: How can I access registers of a terminal, to which an encoder or a valve of an axis is connected? For register communication with terminals to which the encoder or the valve of an axis is connected, it is recommended to use function blocks of types MC_AxUtiReadRegDriveTerm_BkPlcMc [ } 207] (), MC_AxUtiReadRegEncTerm_BkPlcMc [ } 208] (), MC_AxUtiWriteRegDriveTerm_BkPlcMc [ } 215] () and MC_AxUtiWriteRegEncTerm_BkPlcMc [ } 216] (). FAQ #22: What is the structure of an ASCII file for a linearization table? The format of an ASCII file from a linearization table is specified as follows: One linearization point per row.

For each row first a velocity value, then an output value. The velocity values are normalized to the reference velocity. They are therefore in the range -1,000 to 1,000 inclusive. The output values are normalized to the full scale value. They therefore cover the range -1,000 to 1,000. PLC Library Hydraulics 233 Version: 1.4