Knowledge Base fActPosDelta. bEncoderResponse should be used to indicate whether the actual values could be updated. For the sake of uniformity use should again be made here of the fEnc_IncWeighting, fEnc_IncInterpolation and fEnc_ZeroShift or fEnc_RefShift parameters. A range of devices and equipment might be functioning as actuators (Drivetyp), applying a variety of physical principles to create a variable velocity that depends on an electrical magnitude. Depending on the corresponding I/O component, the Drivetype must be set in the selection window and the variables must be linked to the field device.
The Knowledge Base contains a table [ } 225] which supports the selection of the type to be set. If the position measuring system is an incremental system, the corresponding referencing method [ } 79] must also be defined. On the Global tab you should initially enter 100 for the reference velocity. The value is corrected later, but in this way, overlap etc. can be entered directly in %. The acceleration and deceleration should be set to 100 mm/sІ. With this setting, this axis will accelerate to reference velocity in 1 s. The jog parameters should be set to 5 mm/s and 10 mm/s. The creep velocity should be set to 5 mm/sec, the creep distance should be 10 mm and the braking distance 2 mm.
If the valve is covered and the valve data sheet is available, you can enter the overlap from the data sheet on the Valve tab. On the Encoder tab, enter the resolution per increment in Inc. evaluation . Alternatively, an increment number can also be specified in Inc. interpolation and the corresponding path in Inc. evaluation . In the Controller tab, the lag and velocity controller must be set to zero. For further commissioning, a Scope with the following variables should be recorded: SetVelo ActVelo SetPos ActPos fOutput fLagCtrlOutput If available, record pressures, forces and valve slide position. If the controller enable and feed enable of the axis are set, the axis must not move.
If this is the case, a temporary zero balance must be carried out. 5.7.2 Temporary zero compensation The Offset compensation parameter is set in the Controller tab. Depending on the direction in which the axis is drifting, a value between -10 V and +10 V must be entered. As a rule, values of +/- 0.5 V are to be expected. 5.7.3 Movement directions The jog button should be used to move the axis slowly. If this is not the case, the pressure supply must be checked. Furthermore, switching valves may also have to be operated or the compensation of the valve overlap is set too small.
It is recommended to specify a positive direction of movement for the axis that corresponds to the way the machine works. If the axis moves in this direction, the actual position should count upwards. If this is not the case, the counting direction can be inverted on the Encoder tab. If the direction of change of the indicated position corresponds to the mechanical movement, but the direction of action of the given commands is not as desired, the output can be inverted on the Valve tab. PLC Library Hydraulics 261 Version: 1.4