TwinCAT PLC Library Hydraulics - Version 1.4 — 4.3.4 E_TcMcCurrentStep (from V3.0)

PLCopen Motion Control iBufferedCmdEx_Creep : reserved, not implemented. NOTE! #1 If the axis uses a set value generator type without look-ahead, complete commands are entered as a buffer element. NOTE! #2 If the axis uses a set value generator type with look-ahead, commands are split into sections and entered as a package typically consisting of seven buffer elements (jerk, acceleration, jerk, velocity, jerk, deceleration, jerk). 4.3.4 E_TcMcCurrentStep (from V3.0) The constants in this list are used for identifying the internal states of the control value generators. NOTE! Not all of these states are used by all control value generators.

TYPE E_TcMcCurrentStep :( iTcHydStateIdle, iTcHydStateTcAccP, iTcHydStateTcAccM, iTcHydStatePcAccP, iTcHydStatePcAccM, iTcHydStateConstVeloP, iTcHydStateConstVeloM, iTcHydStatePcDecP, iTcHydStatePcDecM, iTcHydStateCreepVeloP, iTcHydStateCreepVeloM, iTcHydStateTcDecP, iTcHydStateTcDecM, iTcHydStateFeedStopPos, iTcHydStateFeedStopNeg, iTcHydStateDoBrake, iTcHydStateCoupling := 1000, iTcHydStateCoupled, iTcHydStateExtCoupled, iTcHydStateExtGenerated := 2000, iTcHydStateEmergencyBreak := 9000, iTcHydStateFault := 9999 ); END_TYPE iTcHydStateIdle: The axis is not actively moving.

Its behavior is controlled by ST_TcHydAxParam.fLagAmp, ST_TcHydAxParam.fTargetClamping and ST_TcHydAxParam.fReposDistance. iTcHydStateTcAccP: The axis establishes a positive control value according to ST_TcHydAxRtData.fDestAcc. This value is set by one of the start function blocks according to the data of the travel command. This state is assumed when the control value reaches the specified motion control value. If the system detects that the braking process for the target approach has to be initiated, the state is changed to iTcHydStatePcDecP . In the absence of feed enable, the state is changed to iTcHydStateFeedStopPos . iTcHydStateTcAccM:

The axis establishes a negative control value according to ST_TcHydAxRtData.fDestAcc. This value is set by one of the start function blocks according to the data of the travel command. This state is assumed when the control value reaches the specified motion control value. If the system detects that the braking process for the target approach has to be initiated, the state is changed to iTcHydStatePcDecM . In the absence of feed enable, the state is changed to iTcHydStateFeedStopNeg . iTcHydStatePcAccP: The axis is in the displacement-controlled acceleration phase of a travelling motion in positive direction.

The control value is set to a value specified by the travel command according to ST_TcHydAxRtData.fDestAcc. The state then changes to iTcHydStateConstVeloP . iTcHydStatePcAccM: The axis is in the displacement-controlled acceleration phase of a travelling motion in negative direction. The control value is set to a value specified by the travel command according to ST_TcHydAxRtData.fDestAcc. The state then changes to iTcHydStateConstVeloM . iTcHydStateConstVeloP: The axis travels in positive direction with constant control value. The control value is specified by the travel command. PLC Library Hydraulics 71 Version: 1.4