Editors In the SFC Options dialog box you can undertake five entries. Under Step Height , you can enter how many lines high an SFC step can be in your SFC editor. 4 is the standard setting here. Under Step Width , you can enter how many columns wide a step should be. 6 is the standard setting here. The Comment Width defines the number of columns, which are shown, if you let the step shown with the comment. You can also preset the Display at Step . With this, you have three possibilities: You can either have Nothing displayed, or the Comment , or the Time Limits . The last two are shown the way you entered them in "Extras" "Step Attributes" .
'Extras' 'Associate Action' With this command actions and Boolean variables can be associated with IEC steps. To the right of, and next to the IEC step, an additional divided box is attached, for the association of an action. It is preset in the left field with the qualifier "N" and the name "Action." Both presets can be changed. For this you can use the Input Assistant. New actions for IEC steps are created in the Object Organizer for an SFC POU with the "Project" "Add Action" command.
'Extras' 'Use IEC-Steps' If this command is activated (denoted by a check in front of the menu item and a printed symbol in the Tool bar), then IEC steps will be inserted instead of the simplified steps upon insertion of step transitions and parallel branches. If this option is switched on, the Init step is set as an IEC step when you create a new SFC POU. The Sequential Function Chart in the Online Mode With the sequential function chart editor in Online mode, the currently-active steps will be displayed as blue steps (black in the example). If you have set it under "Extras" "Options", then the time management is depicted next to the steps.
Under the lower and upper bounds that you have set, a third time indicator will appear from which you can read how long the step has already been active. In the picture above the step depicted has already been active 8 seconds and 410 milliseconds. The step must, however, be active for at least 7 minutes before the step will be left. With "Online" "Toggle Breakpoint" , a breakpoint is set at a step, or in an action at the locations allowed by the language in use. Processing then stops prior to execution of this step or before the location of the action in the program. Steps or program locations where a breakpoint is set are marked in light blue.
If several steps are active in a parallel branch, then the active step whose action will be processed next is displayed in red. If IEC steps have been used, then all active actions in Online mode will be displayed in blue. TX1200 158 Version: 1.3