Reference programming TX1200 231 Version: 1.3 Number Error Message Possible Cause Code too large. Maximum size: ' ' Byte ( K) The maximum program size is exceeded. Reduce project size. 3101 Total data too large. Maximum size: ' ' Byte ( K) Memory is exceeded. Reduce data usage of the application. 3110 Error in library file ' '. The .hex file is not in INTEL Hex format. 3111 Library ' ' is too large. Maximum size: 64K The .hex file exceeds the set maximum size. 3112 Nonrelocatable instruction in library. The .hex file contains a nonrelocatable instruction. The library code cannot be linked. 3113 Library code overwrites function tables. The ranges for code and function tables are overlapping.
3114 Library uses more than one segment. The tables and the code in the .hex file use more than one segment. 3115 Unable to assign constant to VAR IN OUT. _ _ Incompatible data types. The internal pointer format for string constants cannot get converted to the internal pointer format of VAR IN OUT, because the data are _ _ set "near" but the string constants are set " huge" or "far". If possible change these target settings. 3116 Function tables overwrite library code or a segment boundary. Code 166x: The external library cannot be used with the current target settings. These must be adapted resp. the library must be rebuilt with appropriate settings. 3117 ( ): Expression too complex.
No more registers available The named expression is to complex to be handled by the available registers. Please try to reduce the expression by using interim variables. 3120 Current code-segment exceeds 64K. The currently generated code is bigger than 64K. Eventually to much initializing code is created. 3121 POU too large." A POU may not exceed the size of 64K. A POU may not exceed the size of 64K. 3122 Initialisation too large. Maximum size: 64K The initialization code for a function or a structure POU may not exceed 64K. 3123 Data segment too large: segment ' %s', size bytes (maximum bytes) Please contact your manufacturer. 3124 String-constant too large:
characters (Maximum 253 characters) The given constant must be reduced in number of characters. 3130 User-Stack too small: ' ' DWORD needed, ' ' DWORD available. The nesting depth of the POU calls is to big. Enter a higher stack size in the target settings or compile build project without option ‚Debug’ (can be set in dialog ‘Project’ ‘Options’ ‘Build’). 3131 User-Stack too small: ' ' WORD needed, ' ' WORD available. Please contact the PLC manufacturer. 3132 System-Stack too small: ' ' WORD needed, ' ' WORD available. Please contact the PLC manufacturer. 3150 Parameter of function ' ': Cannot pass the result of a IEC-function as string parameter to a C-function.
Use a intermediate variable, to which the result of the IEC function is assigned. 3160 Can't open library file ' '. A library is included in the library manager for this project, but the library file does not exist at the given path. 3161 Library ' ' contains no codesegment A .obj file of a library at least must contain one C function. Insert a dummy function in the .obj file, which is not defined in the .lib file.