PMAC Product Guide Bus Communications 1. Do the bus address jumpers (E91-E92, E66-E71) set an address that matches the bus address that the Executive program is trying to communicate with? 2. Is there something else on the bus at the same address? Try changing the bus address to see if communications can be established at a new address. Address 768 (300 hex) is usually open. Serial Communications 1. Is the proper port on the PC being used? Make sure if the Executive program is addressing the COM1 port, that the COM1 connector has been cabled out. 2. Does the baud rate specified in the Executive program match the baud rate setting of the E44-E47 jumpers on PMAC? 3.

With a breakout box or oscilloscope, make sure there is action on the transmit lines from the PC while typing into the Executive program. If not, there is a problem on the PC end. 4. Probe the return communication line while giving PMAC a command that requires a response (e.g. ). If there is no action, change jumpers E9-E16 on PMAC to exchange the send and receive lines. If there is action but the host program does not receive characters, RS-232 may be receiving circuitry that does not respond at all to PMAC’s RS-422 levels. If there is another model of PC, try using it as a test (most models accept RS-422 levels quite well).

If the computer will not accept the signals, a level-conversion device, such as Delta Tau's Accessory-26 may be needed. Motor Parameters 1. No movement at all. Check the following: a. Are both limits held low to AGND and sourcing current out of the pins? b. Is there proper supply to A+15V, A-15V, and AGND? c. Is the proportional gain (Ix30) greater than zero? d. Can any output at the DAC pin be measured when an O command has been given? e. Is the following error limit being tripped? Increase the fatal following error limit (Ix11) by setting it to a more appropriate value and try to move again. 2. Movement, but sluggish. Check the following: a. Is proportional gain (Ix30) too low?

Try increasing it (as long as stability is kept). b. Is the big step limit (Ix67) too low? Try increasing it to 8,000,000 -- near the maximum -- to eliminate any effect. c. Is the output limit (Ix69) too low? Try increasing it to 32,767 (the maximum) to make sure PMAC can output adequate voltage. d. Can an integrator help? Try increasing integral gain (Ix33) to 10,000 or more, and the integration limit (Ix63) to 8,000,000. 3. Runaway condition. Check the following: a. Is there feedback? Check that position changes can be read in both directions. b. Does the feedback polarity match output polarity? Recheck the polarity match as explained above. 4. Brief movement, then stop.

Check the following: a. Is the following error limit being tripped? Increase the fatal following error limit (Ix11) by setting it to a more appropriate value, and try to move again. If holding position well, but cannot move the motor, the hardware limits are not being held low. Check which limits I125 is addressed to (usually +/-LIM1), then make sure those points are held low (to AGND), and sourcing current (unscrew the wire from the terminal block and put your ammeter in series with this circuit if you need to confirm this). Refer to the Installing and Configuring PMAC section for details on checking the limit inputs. Troubleshooting 93