User Manual of EM730 Series Inverter 105 F08.48 Running time of the fifteenth segment 0.0 ~ 6000.0 s/ min 5.0 ● 0x0830 F09 PID function group F09.00 PID setting source 0: digital PID setting 1: AI1 2: AI2 3: reserved 4: reserved 5: PULSE, high-frequency pulse (X5) 6: communication setting 0 〇 0x0900 F09.01 Digital PID setting 0.0 to PID setting feedback range F09.03 0.0 ● 0x0901 F09.02 PID feedback source 1: AI1 2: AI2 3: reserved 4: reserved 5: PULSE, high-frequency pulse (X5) 6: communication setting 1 〇 0x0902 F09.03 PID setting feedback range 0.1 ~ 6000.0 100.0 ● 0x0903 F09.04 PID positive and negative action selection 0: positive 1:
negative 0 〇 0x0904 F09.05 Proportional gain 1 0.00 ~ 100.00 0.40 ● 0x0905 F09.06 Integral time 1 0.000 ~ 30.000, 0.000: no integral s 2.000 ● 0x0906 F09.07 Differential time 1 0.000 ~ 30.000 ms 0.000 ● 0x0907 F09.08 Proportional gain 2 0.00 ~ 100.00 0.40 ● 0x0908 F09.09 Integral time 2 0.000 ~ 30.000, 0.000: no integral s 2.000 ● 0x0909 F09.10 Differential time 2 0.000 ~ 30.000 ms 0.000 ● 0x090A F09.11 PID parameter switching 0: no switching 1: switching via digital input terminal 0 ● 0x090B