sinee — 6.2Table of functional parameters

User Manual of EM730 Series Inverter 123 injection current F14.77 Acceleration/d eceleration time options of motor 2 0: the same as motor 1 1: acceleration and deceleration time 1 2: acceleration and deceleration time 2 3: acceleration and deceleration time 3 4: acceleration and deceleration time 4 0 〇 0x0E4D F14.78 Maximum frequency of motor 2 20.00 ~ 600.00 Hz 50 〇 0x0E4E F14.79 Upper frequency limit of motor 2 lower limit frequency F00.19 to maximum frequency F14.78 Hz 50 ● 0x0E4F F14.80 V/F curve setting of motor 2 0: straight line V/F 1: multi-point broken line V/F 2: 1.3-power V/F 3: 1.7-power V/F 4: square V/F 5:

VF complete separation mode (Ud = 0, Uq = K * t = voltage of separation voltage source) 6:

VF semi-separation mode (Ud = 0, Uq = K * t = F/Fe * 2 * voltage of separation voltage source) 0 〇 0x0E50 F14.81 Multi-point VF frequency F1 of motor 2 0.00 ~ F14.83 Hz 0.50 ● 0x0E51 F14.82 Multi-point VF voltage V1 of motor 2 0.0~100.0 (100.0 = Rated voltage) % 1.0 ● 0x0E52 F14.83 Multi-point VF frequency F2 of motor 2 F14.81 ~ F14.85 Hz 2.00 ● 0x0E53 F14.84 Multi-point VF voltage V2 of motor 2 0.0 ~ 100.0 % 4.0 ● 0x0E54 F14.85 Multi-point VF frequency F3 of motor 2 F14.83 to rated frequency of motor (reference frequency) Hz 5.00 ● 0x0E55 F14.86 Multi-point VF voltage V3 of motor 2 0.0 ~ 100.0 % 10.0 ● 0x0E56 F14.87 Stop mode of motor 2 0: slow down to stop 1:

free stop 0 〇 0x0E57 F14.96 Low speed correction 10.0 ~ 500.0 % 100.0 ● 0x0E60