sinee — 6.2Table of functional parameters

User Manual of EM730 Series Inverter 131 options VX8 VX7 VX6 VX5 VX4 VX3 VX2 V X 1 0: the VXn status is the same as VYn output status 1: status set by F17.10 F17.10 VX1-VX8 status setting D7 D6 D5 D4 D3 D2 D1 D 0 000 00000 ● 0x110A VX8 VX7 VX6 VX5 VX4 VX3 VX2 V X 1 0: invalid 1:

valid F17.11 VX1 valid delay time 0.000~30.000 s 0.000 ● 0x110B F17.12 VX1 invalid delay time 0.000~30.000 s 0.000 ● 0x110C F17.13 VX2 valid delay time 0.000~30.000 s 0.000 ● 0x110D F17.14 VX2 invalid delay time 0.000~30.000 s 0.000 ● 0x110E F17.15 VX3 valid delay time 0.000~30.000 s 0.000 ● 0x110F F17.16 VX3 invalid delay time 0.000~30.000 s 0.000 ● 0x1110 F17.17 VX4 valid delay time 0.000~30.000 s 0.000 ● 0x1111 F17.18 VX4 invalid delay time 0.000~30.000 s 0.000 ● 0x1112 F17.19 VY1 virtual output function options The same as the function options of digital output terminal of F03 group 0 〇 0x1113 F17.20 VY2 virtual output function options 0 〇 0x1114 F17.21 VY3 virtual output 0 〇 0x1115