User Manual of EM730 Series Inverter F00.03=2: the terminal RUN controls forward running, the terminal Xi is for stop, and the terminal F/R is in the reverse status. ON for reverse running, with valid pulse edges. The terminal Xi is normally closed for stop, The terminal RUN is normally ON for forward running, and the terminal F/R is normally with the valid level. When the inverter is in the running status, press Xi to stop it. When the mode of deceleration to stop (F04.19=0) is selected, the logic diagram is as shown in Fig. 7-7(b). The terminal Xi is for “three-line running and stop control” as defined by F02.00 to F02.04. F00.03=3:
the terminal RUN is for running, Xi for stop and F/R for forward/reverse control. The terminal RUN is normally ON for running, with the valid pulse edge, F/R for forward/reverse switching (forward in the OFF status and reverse in the ON status), and Xi is normally OFF for stop, with the valid level. When the mode of deceleration to stop (F04.19=0) is selected, the logic diagram is as shown in Fig. 7-7(d). ( a ) Wiring diagram of three-line control (F00.03=2) (b)F04.19=0,F00.03=2: forward/reverse running logic 151