sinee — 7.2Motor 1 parameter group of F01 group

User Manual of EM730 Series Inverter the motor is connected to the inverter for the first time, regardless of VF control or vector The above function codes are the nameplate parameters of the asynchronous motor. When control, the above parameters must be correctly set according to the motor nameplate before operation. When the rated power (F01.01) of the motor is changed, the values of F01.03 to F01.08 of the inverter will change automatically. Pay attention to this during operation. are usually unavailable to users. Please get them through motor parameter self-identification The function codes F01.09 to F01.13 are the parameters of the asynchronous motor. They (F01.34).

When the motor parameters (F01.01 to F01.08) are modified, the values of F01.09 to F01.13 of the inverter will change automatically. Pay attention to this during operation. according to the actual situation. Before the motor parameter self-identification, be sure to set F01.00 to F01.08 correctly 168 type Function code Function code name Parameter description Unit Default setting Attribute Mailing address F01.09 Stator resistance of asynchronous motor 1~60000 (rated power of motor: ≤75 kW) 0.1~6000.0 (rated power of motor: > 75kW) mΩ Depending on the motor type 〇 0x0109 F01.10 Rotor resistance of asynchronous motor 1~60000 (rated power of motor: ≤75 kW) 0.1~6000.0 (rated power of motor:

> 75kW) mΩ Depending on the motor type 〇 0x010A F01.11 Leakage inductance of asynchronous motor 0.01 to 600.00 (rated power of motor: ≤75 kW) 0.001 to 60.000 (rated power of motor: > 75 kW) mH Depending on the motor type 〇 0x010B F01.12 Mutual inductance of asynchronous motor 0.1 to 6000.0 (rated power of motor: ≤75 kW) 0.01 to 600.00 (rated power of motor: > 75 kW) mH Depending on the motor type 〇 0x010C F01.13 No-load excitation current of asynchronous motor 0.01 to 600.00 (rated power of motor: ≤75 kW) 0.1 to 6000.0 (rated power of motor: > 75 kW) A Depending on the motor type 〇 0x010D