sinee — 7.3Function Parameter Group of Input Terminal of F02

User Manual of EM730 Series Inverter The analog input terminals AI1 and AI2 of the EM730 series inverter can be used as digital input terminals. You only need to set the corresponding bit to 1. To use the AI2 terminal as a digital terminal, you only need to set F02.31=xx1x. The analog input and digital logic conversion are as follows:  When the input voltage of the terminal is less than 1V, its corresponding logic status  When the input voltage of the terminal is greater than 3V, its corresponding logic will be invalid; status will be valid;  When the input voltage of the terminal is within [1V, 3V], its corresponding logic status will remain unchanged. Fig.

7-10 Correspondence between Analog Input Terminal Voltage and Current Logic Status If it is used as an analog input terminal, the filter time and corresponding offset curve can be set via F02.32 to F02.60. The terminals AI1 to AI2 can be set separately. 182 Function code Function code name Parameter description Unit Default setting Attribute mailing address F02.31 Options of analog input function Ones place: AI1 0: analog input 1: digital input (0 below 1V, 1 above 3V, the same as last time under 1~3V) Tens place: AI2 0: analog input 1:

digital input (the same as above) 00D 〇 0x021F Function code Function code name Parameter description Unit Default setting Attribute mailing address F02.32 Options of analog input curve Ones place: options of AI1 curve 0: curve 1 1: curve 2 10 〇 0x0220