sinee — 7.4Function Parameter Group of Output Terminal of F03

User Manual of EM730 Series Inverter 187 output will remain unchanged. See the description of the function codes F15.21 and F15.22. 4 Output frequency detection FDT2 When the |output frequency| is greater than the result of output frequency detection FDT2 (F15.23) in the running status, the current output will be valid. When the inverter is not in the running status, or the |output frequency| is less than or equal to the result of output frequency detection FDT2 (F15.23) minus FDT2 hysteresis (F15.24), the current output will be invalid. In other statuses, the current output will remain unchanged. See the description of the function codes F15.23 and F15.24.

5 Reverse running (REV) When the running direction and acceleration/deceleration of the inverter is in the status of reverse acceleration, reverse deceleration or reverse constant speed, the current output will be valid. In other statuses, the current output will be invalid. 6 Jog When the inverter is in the status of JOG running or JOG stop, the current output will be valid. In other statuses, the current output will be invalid. 7 Inverter protection The current output will be valid when the inverter is in the protection status and invalid when the inverter is in other statuses.

8 Inverter ready to run (READY) When the inverter has been powered on and completely initialized without any abnormality, the current output will be valid. When the inverter is not suitable for running, the current output will be invalid. 9 Reach the upper frequency limit When the inverter is in the JOG or slave running status, the output frequency (F18.00) is greater than or equal to the upper frequency limit (F00.17||F00.18), and the set frequency (F18.01) is greater than or equal to the upper frequency limit (F00.17||F00.18), the current output will be valid. Otherwise, the current output will be invalid.

10 Reach the lower frequency limit When the inverter is in the JOG or slave running status, the output frequency (F18.00) is less than or equal to the lower frequency limit (F00.19), and the set frequency (F18.01) is less than or equal to the lower frequency limit (F00.19), the current output will be valid. Otherwise, the current output will be invalid. 11 Valid current limit When the output current (F18.06) is greater than or equal to