User Manual of EM730 Series Inverter voltage is higher than the instantaneous stop/non-stop recovery voltage (F07.09), the inverter will not slow down. When the cumulative time reaches the judgement time for instantaneous stop/non-stop recovery voltage (F07.10), the inverter will start to acceleration, and the frequency will gradually return to the set value. When the ones place of the instantaneous stop/non-stop option of F07.06 bus voltage control is set to “2: Slow down to stop”, the action is similar to that of the option 1.
When the bus voltage reaches the instantaneous stop/non-stop action voltage, the speed set based on the instantaneous stop/non-stop slowdown time (F07.30) will constantly decrease to 0, regardless of voltage recovery. Fig. 7-24 Schematic Diagram of Instantaneous Stop/Non-stop Deceleration Function F07.11=0: invalid The current limit does not work. 222 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F07.11 Current limit control 0: invalid 1: limit mode 1 2: limit mode 2 2 〇 0x070B F07.12 Current limit level 20.0 ~180.0 (100% = rated current of inverter) % 150.0 ● 0x070C