User Manual of EM730 Series Inverter F09.00=6: communication setting The percentage of PID setting depends directly on the communication (percentage). If the master-slave communication (F10.05=1) is enabled and the inverter works as the slave (F10.06=0), the specific setting percentage is “700FH (master-slave communication setting) * F10.08 (slave receiving proportional coefficient)”, and the 700FH data range is -100.00% to 100.00%, as detailed in Table 12-31. For the general communication (F10.05=0), the specific setting percentage is “7004H (communication setting of process PID setting)”, and the 7004H data range is -100.00% to 100.00%, as detailed in Table 12-31.
F09.02=1:AI1 F09.02=2: AI2 The PID feedback percentage is directly dependent on the AI (percentage). For the details of AI1 to AI2, see the description of F00.04. When is used as the PID feedback, the percentage will directly turn the feedback value, and the maximum output is 100.00%. F09.02=5: PULSE high-frequency pulse (X5) The set percentage of PID is directly dependent on the HDI (percentage). For the details of AI1-AI2 and X5, see the description of F00.04. When used as the PID setting, the percentage will directly turn the set value, and the maximum output is 100.00%. F09.02=6: communication setting The PID feedback percentage is directly dependent on the communication (percentage).
If the master-slave communication (F10.05=1) is enabled and the inverter works as the slave (F10.06=0), the specific feedback percentage is “700FH (master-slave communication setting) * F10.08 (slave receiving proportional coefficient)”, and the 239 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F09.02 PID feedback source 1: AI1 2: AI2 3: reserved 4: reserved 5: PULSE, high-frequency pulse (X5) 6: communication setting 1 〇 0x0902