sinee — 7.16Auxiliary Function Parameter Group of F15 Group

User Manual of EM730 Series Inverter See F05.00 to F05.06 See F04.19 7.16 Auxiliary Function Parameter Group of F15 Group As shown in Fig. 7- 32, when the jog running command (FJOG/RJOG) is valid, the inverter will start running at the set frequency of F15.00; and when the jog running command is invalid, the inverter will be stopped according to the stop mode. values (e.g. 500) depend on the acceleration and deceleration time unit (F15.13), and have F15.01 and F15.02 are set as the acceleration and deceleration time during operation. Their different meanings and ranges.

For example, F15.13=0 means that the acceleration and deceleration time is 5.00s, and F15.13=1 means that the acceleration and deceleration time is 50.0s. 273 F14.85 Multi-point VF frequency F3 of motor 2 F14.83 to rated frequency of motor (reference frequency) Hz 5.00 ● 0x0E55 F14.86 Multi-point VF voltage V3 of motor 2 0.0~100.0 % 10.0 ● 0x0E56 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F14.87 Stop mode of motor 2 0: slow down to stop 1:

free stop 0 〇 0x0E57 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F15.00 Jog frequency 0.00 to maximum frequency F00.16 Hz 5.00 ● 0x0F00 F15.01 Jog acceleration time 0.00 ~ 650.00 (F15.13=0) 0.0 ~ 6500.0 (F15.13=1) 0 ~ 65000 (F15.13=2) s 5.00 ● 0x0F01 F15.02 Jog deceleration time 0.00 ~ 650.00 (F15.13=0) 0.0 ~ 6500.0 (F15.13=1) 0 ~ 65000 (F15.13=2) s 5.00 ● 0x0F02