sinee — 7.17F16 customized function parameter group

User Manual of EM730 Series Inverter F16.00=3: Winding application The inverter is a dedicated PID-regulated control product for winding and unwinding. F16.00=4: Fan application The inverter can be used to configure the parameters of the corresponding function code for the fan application macro. 289 0.0~6500.0(F15.13=1) 0~65000(F15.13=2) F00.19 Lower frequency 0.00~Upper frequency limit F00.18 Hz 30.00 ● 0x0013 F00.21 Inversion of Control 0: Allow forward/reverse rotation 1: Disable reverse rotation 1 〇 0x0015 F00.24 Automatic adjustment of carrier frequency 0: Invalid 1: Valid 1 2:

Valid 2 0 〇 0x0018 F02.01 X2 Digital input function selection See the input terminal function table for details. 9 〇 0x0201 F02.37 Curve 2 Minimum Input -10.00~F02.39 V 2.10 ● 0x0225 Function code Function code name Parameter description Uni t Default setting Attribut e Mailing address F00.02 Command source selection 0: Keyboard control (LOC/REM light on) 1: Terminal control (LOC/REM light off) 2: Communication control (LOC/REM light flashing) 1 〇 0x0002 F00.04 Main frequency source A selection 0: Digital frequency given F00.07 1: AI1 2: AI2 5: High frequency pulse input (X5) 2 〇 0x0004