User Manual of EM730 Series Inverter The terminals VY1 to VY8 essentially have the same function, but there are no corresponding physical terminals actually. They all have the positive and negative logic functions. The terminals VY1 to VY4 have the delay function, and their statuses can be confirmed in the same way. They can be set separately. The terminal VY1 is taken as an example below. F17.28=xxxxxxx0: the VY1 status is the same as the actual input status of X1.
312 function options F17.25 VY7 virtual output function options 0 〇 0x1119 F17.26 VY8 virtual output function options 0 〇 0x111A F17.27 Virtual output positive/negative logic D7 D6 D5 D4 D3 D2 D1 D0 000 00000 〇 0x111B VY8 VY7 VY6 VY5 VY4 VY3 VY2 VY1 0: positive logic, valid in the closed state/invalid in the open state 1:
negative logic, invalid in the closed state/valid in the open state F17.29 VY1 valid delay time 0.000~30.000 s 0.000 ● 0x111D F17.30 VY1 invalid delay time 0.000~30.000 s 0.000 ● 0x111E F17.31 VY2 valid delay time 0.000~30.000 s 0.000 ● 0x111F F17.32 VY2 invalid delay time 0.000~30.000 s 0.000 ● 0x1120 F17.33 VY3 valid delay time 0.000~30.000 s 0.000 ● 0x1121 F17.34 VY3 invalid delay time 0.000~30.000 s 0.000 ● 0x1122 F17.35 VY4 valid delay time 0.000~30.000 s 0.000 ● 0x1123 F17.36 VY4 invalid delay time 0.000~30.000 s 0.000 ● 0x1124 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F17.28 Control options of virtual output terminal D7 D6 D5 D4 D3 D2 D1 D0 111 11111 〇 0x111C VY8 VY7 VY6 VY5 VY4 VY3 VY2 VY1 0:
depending on the status of terminal X1-X5 (without VY6-8) 1: depending on the output function status