sinee — 7.22Water supply application macro description

User Manual of EM730 Series Inverter 4.2 Sending a frame of discontinuous addresses using the address mapping function PLC needs to read EM730 inverter data, including output frequency, output current, PID given, digital input terminal state. As the above four data addresses are discontinuous, PLC needs to send 4 frames of data to read respectively, through the address mapping function can realize PLC send a frame of data to read the above 4 original discontinuous data. Map F18.00, F18.01, F18.02, and F18.03 to F18.00, F18.06, F18.16, and F18.22 respectively. Mapping parameters are set as follows:

F45.00=1 (mapping function is valid) F45.01=4608 (Source address 1) F45.02=4608 (destination address 1) F45.04=4609 (Source address 2) F45.05=4614 (destination address 2) F45.07=4610 (Source address 3) F45.08=4624 (Destination ADDRESS 3) F45.10=4611 (source address 4) F45.11=4630 (destination address 4) 7.22 Water supply application macro description Function introduction 1. After selecting the water supply macro, the status parameters that need to be paid attention to in water supply have been preset: output frequency, set pressure, feedback pressure, output current, analog feedback AI2 value (%), press the shift key to switch. 2.

After selecting the water supply macro, you can adjust the given pressure by rotating the 339 Source address 1 F18.00 (1200H/4608D) Destination address 1 F18.00 (1200H/4608D) Output frequency Source address 2 F18.01 (1201H/4609D) Destination address 2 F18.06 (1206H/4614D) Output current Source address 3 F18.02 (1202H/4610D) Destination address 3 F18.16 (1210H/4624D) PID given Source address 4 F18.03 (1203H/4611D) Destination address 4 F18.22 (1216H/4630D) Digital input terminal state