sinee — 1.1.1.30x42: function code used to write multiple registe

User Manual of EM730 Series Inverter  Response PDU  Error PDU deceleration time 1 (F00.15) to 6.00: Below is an example of a request to set the acceleration time 1 (F00.14) to 5.00 and ★ This function code cannot be used to change the parameters of the attribute “○” (it cannot be changed during operation). That is, only the parameters of the attribute “●” (it can be changed during operation) can be changed. Otherwise, the error code 1 will be returned.

374 Function code 1 byte 0x42 Starting Address 2 bytes 0x0000 - 0xFFFF Number of registers 2 bytes 1 - 16 Error code 1 byte 0xC2 Exception code 1 byte See Table 4-33 Request Respond Domain name (0x) Domain name (normal) (0x) Domain name (abnormal) (0x) Function 42 Function 42 Function C2 Starting address Hi 00 Starting address Hi 00 Exception code 03 Starting address Lo 0E Starting address Lo 0E Number (Hi) of registers 00 Number (Hi) of registers 00 Number (Lo) of registers 02 Number (Lo) of registers 02 Number of bytes 04 Register value Hi (F00.14) 01 Register value Lo (F00.14) F4 Register value Hi (F00.15) 02 Register value Lo (F00.15) 58