User Manual of EM730 Series Inverter 381 protection (including option card) 7015H Communication setting of main channel frequency A 0.00 to maximum frequency 7016H Communication setting of auxiliary channel frequency B 0.00 to maximum frequency 7017H Communication setting of upper frequency limit 0.00 to maximum frequency 7018H Communication setting of upper frequency limit of torque control 0.00 to maximum frequency 7019H Communication setting of upper torque limit of speed control 0.0 to 250.0% (based on 100.0% or direct sending) 701AH Communication setting 1 Communication setting by M1 terminal, communication address option 701AH 701CH~71FF H Reserved Working status 7200H ~ 73FFH 7200H status word 1 Bit7 to 0 running status 00H Parameter setting 01H Slave running 02H JOG running 03H Self-learning running 04H Slave stop 05H JOG stop 06H Protection status 07H Factory self-inspection 08H - 0FFH Reserved Bit15-8 protection information 00H Normal running of inverter xxH Inverter protection status, where “xx” is the protection code 7201H status word 2 Bit0 setting direction 1 - setting is valid 0 + setting is valid Bit1 running direction 1 Reverse frequency output 0 Forward frequency output