User Manual of EM730 Series Inverter 76 F01.07 Rated power factor of motor 0.600~1.000 Depen ding on the motor type 〇 0x0107 F01.08 Motor efficiency 30.0~100.0 % Depen ding on the motor type 〇 0x0108 F01.09 Stator resistance of asynchronous motor 1~ 60000 (rated power of motor: ≤75 kW) 0.1~6000.0 (rated power of motor: > 75kW) mΩ Depen ding on the motor type 〇 0x0109 F01.10 Rotor resistance of asynchronous motor 1~ 60000 (rated power of motor: ≤75 kW) 0.1~6000.0 (rated power of motor: > 75kW) mΩ Depen ding on the motor type 〇 0x010A F01.11 Leakage inductance of asynchronous motor 0.01 to 600.00 (rated power of motor: ≤75 kW) 0.001 to 60.000 (rated power of motor:
> 75 kW) mH Depen ding on the motor type 〇 0x010B F01.12 Mutual inductance of asynchronous motor 0.1 to 6000.0 (rated power of motor: ≤75 kW) 0.01 to 600.00 (rated power of motor: > 75 kW) mH Depen -ding on the motor type 〇 0x010C F01.13 No-load excitation current of asynchronous motor 0.01 to 600.00 (rated power of motor: ≤75 kW) 0.1 to 6000.0 (rated power of motor: > 75 kW) A Depen ding on the motor type 〇 0x010D F01.14 Flux weakening coefficient 1 of asynchronous motor 10.00 ~ 100.00 % 87.00 〇 0x010E F01.15 Flux weakening 10.00 ~ 100.00 % 80.00 〇 0x010F