sinee — 6.2Table of functional parameters

User Manual of EM730 Series Inverter 83 inflection point 1 of curve 4 F02.52 Input setting of inflection point 1 of curve 4 –100.0 ~ +100.0 % -50.0 ● 0x0234 F02.53 Input of inflection point 2 of curve 4 F02.51 ~ F02.55 V 5.00 ● 0x0235 F02.54 Input setting of inflection point 2 of curve 4 –100.0 ~ +100.0 % 50.0 ● 0x0236 F02.55 Maximum input of curve 4 F02.53 ~ 10.00 V 9.90 ● 0x0237 F02.56 Maximum input setting of curve 4 –100.0 ~ +100.0 % 100.0 ● 0x0238 F02.57 AI1 filtering time 0.00 ~ 10.00 s 0.10 ● 0x0239 F02.58 AI2 filtering time 0.00 ~10.00 s 0.10 ● 0x023A F02.60 Reserved 0x023C F02.61 AD hysteresis code 2 ~ 50 2 〇 0x023D F02.62 Selection of analog input AI1 type 0: 0~10V 3: -10~10V 4:

0~5V 0 〇 0x023E F02.63 Selection of analog input AI2 type 0: 0~10V 1: 4~20mA 2: 0~20mA 4: 0~5V 0 0x023F F02.66 Selection of AI2 current input impedance 0: 500Ω 1: 250Ω 0 〇 0x0242 F03 Output terminal function group F03.00 Options of Y1 output function 0: no output 1: inverter running (RUN) 2: up to output frequency (FAR) 1 〇 0x0300