sinee — 6.2Table of functional parameters

User Manual of EM730 Series Inverter 92 F06.17 SVC zero-frequency processing 0: braking 1: not processed 2: seal the tube 2 〇 0x0611 F06.18 SVC zero-frequency braking current 50.0 ~ 400.0 (100.0 is the no-load current of the motor) % 100.0 〇 0x0612 F06.20 Voltage feedforward gain 0 ~ 100 % 0 ● 0x0614 F06.21 Flux weakening control options 0: invalid 1: direct calculation 2:

automatic adjustment 2 〇 0x0615 F06.22 Flux weakening voltage 70.00 ~ 100.00 % 95.00 ● 0x0616 F06.23 Maximum field weakening current of synchronous motor 0.0 ~ 150.0 (100.0 is the rated current of the motor) % 100.0 ● 0x0617 F06.24 Proportional gain of flux weakening regulator 0.00 ~ 10.00 0.50 ● 0x0618 F06.25 Integral time of flux weakening regulator 0.01 ~ 60.00 s 2.00 ● 0x0619 F06.26 MTPA control option of synchronous motor 0: invalid 1: valid 1 〇 0x061A F06.27 Self-learning gain at initial position 0 ~ 200 % 100 ● 0x061B F06.28 Frequency of low frequency band of injection current 0.00 ~ 100.00 (100.00 is the rated frequency of the motor) % 10.00 ● 0x061C