sinee — 6.6.3 Detection of output frequency reaching se

User Manual of EM760 High-Performance Inverter Fig. 6-28 Output frequency detection range FDT 6.6.3 Detection of output frequency reaching setting (FAR) Fig. 6-29 Schematic Diagram of FAR Detection As shown in the figure above, when the multi-function output terminal or relay output is set to “2: up to output frequency (FAR)”, and the absolute value of the difference between the |output frequency| and |given frequency| is less than or equal to the set value ofFAR detection width (F15.20) during inverter operation, the corresponding function terminal will output the active level. Otherwise, this terminal will output the inactive level.

149 Function code Function codename Parameter description Unit Default setting Attribute F15.20 Detection width of output frequency arrival (FAR) 0.00~50.00 Hz 2.50 O