User Manual of EM760 High-Performance Inverter When the pulse frequency exceeds 250Hz (=1/(2 (default filtering times)*2*1ms -1 )), make sure ofthe input through the high-speed pulse input terminal (X7), and set F02.06 to “35: high-speed count input”. 250Hz is only a theoretical value. The actual effect will prevail. In order to avoid errors, use the high-speed pulse input terminal wherever possible. Fig. 6-33 Example of Counting The figure above shows an example, where F16.03=8 and F16.04=5. When the count reaches the specified value 5, the output of “15: reach the specified value” will be valid. When the count reaches the set value 8, the output of “14: reach the set value” will be valid.
When the input of “36: clear length” is valid, the count will be cleared to 0, and the outputs of“15: reach the specified value” and “ 14: reach the set value” will be invalid. Limit 65535 ≥set count ≥specified count ≥0. If the set count and specified count are 0, the counter function will be invalid. This function is allowed for one terminal only at a time. 6.6.13 Fixed length function 155 Function code Function codename Parameter description Unit Default setting Attribute F16.01 Set length 1~65535(F16.13=0) 0.1~6553.5(F16.13=1) 0.01~655.35(F16.13=2) 0.001~65.535(F16.13=3) m 1000 ● F16.02 Pulses per meter 0.1~6553.5 100.0 ● F16.13 Set length resolution 0: 1m 1: 0.1m 2: 0.01m 3: 0.001m 0 O