sinee — 6.9.1.1 Water supply app

User Manual of EM760 High-Performance Inverter 172 F09.03 PID setting feedback range 0.01~600.00 bar 10.00 ● F09.05 Proportional gain 1 0.00~100.00 3.00 ● F09.06 Integral time 1 0.000 - 30.000, 0.000: no integral s 1.000 ● F09.27 PID sleep control options 0: Invalid 1: sleep at zero speed 2: sleep at lower frequency limit 3: sleep with tube sealed 0 ● F09.28 Sleep action point 0.00-100.00 (100.00 corresponds to the PID setting feedback range) % 100.00 ● F09.29 Sleep delay time 0.0~6500.0 s 60.0 ● F09.30 Wake-up action point 0.00-100.00 (100.00 corresponds to the PID setting feedback range) bar 2.00 ● F09.31 Wake-up delay time 0.0~6500.0 s 0.5 ● F09.39 Wake-up option 0:

target pressure F09.01* coefficient of wake-up action point 1: Wake-up action point (F09.30) 1 O F09.40 Coefficient of wake-up action point 0.0-100.0 (100% corresponds to PID setting) % 80.0 ● F09.41 Pipeline network alarm overpressure 0.0 to pressure sensor range F09.03 % 8.0 ● F09.42 Overpressure protection time 0-3600 (0: invalid) s 0 ● F09.44 Sleep mode options 0: Sleep at sleep frequency (F09.45) 1:

Sleep at sleep action points (F09.28) 0 O F09.45 Sleep frequency 0.00 to upper frequency limit F00.18 Hz 30 ● F12.33 Running status display parameter 1 of mode 1 (display parameter 5 of LED stop status) 0.00~99.99 18.00 ● F12.34 Running status display parameter 2 of mode 1 (display parameter 1 of LED stop status) 0.00~99.99 18.01 ● F12.35 Running status display parameter 3 of mode 1 (display parameter 2 of LED stop status) 0.00~99.99 18.06 ●