User Manual of EM760 High-Performance Inverter 313 F09.45 Sleep frequency 0.00 to upper frequency limit F00.18 Hz 30.00 ● 0x092D F09.46 PID feedback increment 0~100 5 ● 0x092E F09.47 PID non-responsive feedback interval 0.00~600.00 bar 0.02 ● 0x092F F10 Communication function group F10.00 Local Modbus communication address 1-247; 0: broadcast address 1 O 0x0A00 F10.01 Baud rate of Modbus communication 0: 4800 1: 9600 2: 19200 3: 38400 4: 57600 5: 115200 1 O 0x0A01 F10.02 Modbus data format 0: 1-8-N-1 (1 start bit + 8 data bits + 1 stop bit) 1: 1-8-E-1 (1 start bit + 8 data bits + 1 even parity check bit + 1 stop bit) 2:
1-8-O-1 (1 start bit + 8 data bits + 1 odd parity check bit + 1 stop bit) 3: 1-8-N-2 (1 start bit + 8 data bits + 2 stop bits) 4: 1-8-E-2 (1 start bit + 8 data bits + 1 even parity check bit + 2 stop bits) 5: 1-8-O-2 (1 start bit + 8 data bits + 1 odd parity check bit + 2 stop bits) 0 O 0x0A02 F10.03 Communication timeout 0.0s-60.0s; 0.0: invalid (valid for the master- slave mode) s 0.0 ● 0x0A03 F10.04 Modbus response delay 1~20 ms 2 ● 0x0A04 F10.05 Options of master- slave communication function 0: Invalid 1: valid 0 O 0x0A05